General Summary of Design Criteria

Summary of Design Criteria

Raw Water Intake Pump Station (Existing)
Number of Pumps
Pump Type
Capacity (each)
TDH (each)
Motor Size
Motor Speed

3 duty, 1 standby
Vertical Turbine
2 @ 1,100 gpm, 1 @ 645 gpm, 1 @ 400 gpm
235 ft
2 @ 75 HP, 1 @ 50 HP, 1 @ 30 HP
Constant speed
Chemical Feed Systems
Alum Feed System
Form
Chemical Storage Tank
Pump Quantity
Pump Type
Design Concentration
Addition Point


Liquid
275-gal tote or 50-gal drum
1 duty
Diaphragm Metering Pump
1-5 mg/L
Raw Water
Polymer Feed System 1 (currently Aqua
Hawk 2987)
Form
Chemical Storage Tank
Pump Quantity
Pump Type
Design Concentration
Addition Point


Liquid Cationic
275-gal tote or 50-gal drum
1 duty
Diaphragm Metering Pump
1-5 mg/L
Raw Water
Polymer Feed System 2 (currently Vikchem
201)

Form
Chemical Storage Tank
Pump Quantity
Pump Type
Design Concentration
Addition Point


Dry Anionic
50-gal tank & mixer
1 duty
Diaphragm Metering Pump
0.1-0.2 mg/L
Raw Water
Filter Aid Feed System
Form
Chemical Storage Tank
Pump Quantity
Pump Type
Addition Point

Liquid
50-gal tank
1 duty
Diaphragm Metering Pump
Treated Water
Contact Adsorption Clarifiers (CAC)
Treatment Capacity
CAC Firm Capacity


2.65 MGD (21 hrs x 3 trains)
CAC Equipment
Type
Quantity
Unit Capacity (each)
Firm Capacity
Dimensions (each tank)
Dry Weight (each tank)
Operating Weight (each tank)
Tank Material
Loading Rate Capacity

Upflow, buoyant media
4 (3 duty, 1 standby)
700 gpm
2,100 gpm
12 ft (L) x 9 ft (W) x 9 ft (H)
18,500 lbs
45,000 lbs
Painted Steel
10 gpm/ft2
CAC Backwash
Type
Rate (each)
Flow Required
Duration
Blower Quantity
Blower Capacity
Blower Motor

Water and air
10 gpm/ ft2
700 gpm
~ 10 minutes
3 (2 duty, 1 standby)
350 scfm each
20 HP, constant speed
CAC Buoyant Media
Type
Depth
Area (each)

50% Fiber Balls and 50% Plastic Beads
48-inches
70 ft2
Media Filtration
Media Filters
Type
Quantity
Dimensions (each)
Filter Area (each)
Peak Filtration Rate (@ 2,100 gpm)
Backwash Rate (each)
Media Type
Underdrain System
Water Depth Over Media
Filter Headloss Available (max.)


Rapid rate gravity
4
12 ft (L) x 15 ft (W) x 18 ft (D)
180 ft2
3.9 gpm/ft2
20 gpm/ft2 (max)
Dual media (anthracite/silica sand)
Thermoplastic block, media retaining
11.5 ft
8.0 ft
Filter Backwash Pumps
Quantity
Type
Capacity (each)
Head
Motor

3 (lead, lag, standby)
Vertical in-line
1,800 gpm
12 feet
15 HP, constant speed
Filter Backwash Air Scour Blower
Quantity
Type
Capacity
Backwash Air Rate (per filter)
Pressure
Motor

1 duty
Rotary lobe
720 scfm
4 scfm/ ft2
7.5 psi
50 HP, constant speed
Chlorine Equipment
Regulator
Capacity (max.)
Type
Number


100 lbs/day
Cylinder mount, vacuum
2
Automatic Switchover Valve
Capacity (max.)
Number

100 lbs/day
1
Auto Control Valve
Capacity (max.)
Configuration
Number

100 lbs/day
Flow/residual pacing
1 (standby manual rotometer)
Scale
Capacity
Number (cylinders)

300 lbs
2
Gas Monitoring
Chlorine
Number

0-10 ppm
1
High Lift Pumps
Quantity
Type
Capacity (each)
Head
Motor

3
Vertical turbine
1,200 gpm
190 ft
75 HP, variable speed
Backwash Waste Pump Station
Backwash Waste Pumps
Quantity
Type
Capacity (each)
Head
Motor


2
Vertical turbine
500 gpm
142 ft
25 HP, variable speed
Highland Booster Pump Station
Booster Pumps
Quantity
Type
Capacity (each)
Head
Motor


3
Horizontal split case
1,000 gpm
140 ft
75 HP, variable speed