Process Control Equipment
Number | Description | Location | |
PI | 100 | Existing Pressure Indicator | Existing Raw Water Well |
FIT/FE | 100-1 | Venturi Flow Meter | Control Valve Vault |
FCV | 100-1 | RW Flow Control Valve | Control Valve Vault |
PIT | 100-1 | Pressure Transmitter | Control Valve Vault |
YS | 100-1 | Door Switch | Control Valve Vault |
LSH | 100-1 | Sump Level Switch | Intake Valve Chamber |
FIT/FE | 100-2 | RW Magnetic Flow Meter | Raw Water Corridor |
AIT/AE | 100-1 | RW Turbidimeter Element/Transmitter | High Lift Pump Area |
AIT/AE | 100-2 | pH Analyzer Element/Transmitter | High Lift Pump Area |
SOV | 100-1 | SA Solenoid Valve | Raw Water Corridor |
AIT/AE | 200-1 | pH Analyzer Element/Transmitter | Raw Water Corridor |
SOV | 200-1 | RW SA Solenoid Valve | Raw Water Corridor |
PI | 200-2-1,2,3 | CAC Blower Discharge Pressure Indicator | CAC Blower Room |
PSH | 200-2 | CAC Blowers Discharge Pressure Switch | CAC Blower Room |
PE/PI | 200-1 | CAC Inlet Pressure Indicator | CAC Blower Room |
FCV | 200-1-1,2,3,4 | CAC Influent RW Flow Control Valve | CAC Process Area |
FIT/FE | 200-1,2,3 | CAC Influent RW Magnetic Flow Meter | CAC Process Area |
PSHH | 200-1-1,2,3,4 | CAC High-High Pressure Switch | CAC Process Area |
PSH | 200-1-1,2,3,4 | CAC High Pressure Switch | CAC Process Area |
PI | 200-1-1,2,3,4 | CAC Pressure Indicator | CAC Process Area |
PIT | 200-1 | CAC RW Pressure Transmitter | CAC Process Area |
FCV | 200-2-1,2,3,4 | CAC TW Flow Control Valve | CAC Process Area |
FCV | 200-3-1,2,3,4 | CAC ALP Flow Control Valve | CAC Process Area |
YS | 200-1 | Water on Floor Alarm | CAC Process Area |
AIT/AE | 200-2-1 | Combined TW Turbidimeter | CAC Process Area |
SOV | 200-2 | Combined TW SA Solenoid Valve | CAC Process Area |
FCV | 300-1-1,2,3,4 | TW Flow Control Gate | Filter Process Area |
FCV | 300-2-1,2,3,4 | FE Flow Control Valve | Filter Process Area |
FCV | 300-3-1,2,3,4 | BWS Flow Control Valve | Filter Process Area |
FCV | 300-4-1,2,3,4 | FTW Flow Control Valve | Filter Process Area |
FCV | 300-5-1,2,3,4 | BWW Flow Control Valve | Filter Process Area |
FCV | 300-6-1,2,3,4 | ALP Flow Control Valve | Filter Process Area |
LIT/LE | 300-1,2,3,4 | Filter Ultrasonic Level Element/Transmitter | Filter Process Area |
DPE/DPIT | 300-1,2,3,4 | Filter Differential Pressure Transducer/Transmitter | Filter Process Area |
AIT/AE | 300-1-1,2,3,4 | FE Turbidimeter Element/Transmitter | Filter Process Area |
SOV | 300-1,2,3,4 | FE SA Solenoid Valve | Filter Process Area |
AIT/AE | 300-2-1 | CFE Turbidimeter Element/Transmitter | Filter Process Area |
SOV | 300-5 | CFE SA Solenoid Valve | Filter Process Area |
FIT/FE | 300-1-1 | CFE Magnetic Flow Meter | Filter Process Area |
YS | 300-1 | Water on Floor Alarm | Filter Process Area |
LIT/LE | 300-5 | Ultrasonic Level Element/Transmitter | Chlorine Contact Basin |
AIT/AE | 300-3-1 | Residual Chlorine Analyzer/Transmitter | Raw Water Corridor |
SOV | 300-6 | FE SA Solenoid Valve | Raw Water Corridor |
LIT/LE | 400-1 | Ultrasonic Level Element/Transmitter | Clearwell |
LSH | 400-1 | High Level Switch | Clearwell |
LSL | 400-1 | Low Level Switch | Clearwell |
PI | 400-1,2,3 | Pump Pressure Indicator | High Lift Pump Area |
FIT/FE | 400-1 | FW Magnetic Flow Meter | High Lift Pump Area |
PE/PIT | 400-1 | High Lift Pump Pressure Element/Transmitter | High Lift Pump Area |
FIT/FE | 400-2 | Plant PW Magnetic Flow Meter | High Lift Pump Area |
AIT/AE | 400-1 | FW pH Meter/Transmitter | High Lift Pump Area |
AIT/AE | 400-2 | FW Residual Chlorine Analyzer/Transmitter | High Lift Pump Area |
AIT/AE | 400-3 | Potable Water Turbidimeter/ Transmitter | High Lift Pump Area |
SOV | 400-1 | Potable Water Sample Solenoid Valve | High Lift Pump Area |
SOV | 500-1 | Chlorine Injection Sample Solenoid Valve | Chlorine Room |
PI | 500-1,2 | Chlorinator Pressure Indicator | Chlorine Room |
QS | 500-1 | Chlorinator Low Vacuum Switch | Chlorine Room |
M | 500-1 | Chlorinator | Chlorine Room |
AE/AIT | 500-1 | Chlorine Leak Detector Element/Transmitter | Chlorine Room |
XA | 500-1 | Chlorine Leak Detector Beacon | Chlorine Room |
WE/WIT | 500-1 | Chlorine Cylinder Weight Element/Transmitter | Chlorine Room |
WE | 500-2 | Chlorine Cylinder Weight Scale | Chlorine Room |
TIT/TE | 500-1 | Room Temperature Element/Transmitter | Chlorine Room |
TIT/TE | 500-2 | Room Temperature Element/Transmitter | Electrical Room |
PE/PIT | 300-1 | Pump Pressure Element/Transmitter | BWS Pump Area |
PI | 300-1-1,2,3 | Pump Discharge Pressure Indicator | BWS Pump Area |
PSH | 300-1-1,2,3 | Pump Discharge High Pressure Switch | BWS Pump Area |
FIT/FE | 300-2-1 | BWS Magnetic Flow Meter | BWS Pump Area |
LSH | 700-1 | High Level Switch | Sludge Sump |
LIT/LE | 700-1 | Level Element/Transmitter | BWW Pump Station |
LSH | 700-2 | High Level Switch | BWW Pump Station |
FCV | 300-7-1 | Blower Vent Flow Control Valve | Filter Blower Area |
PI | 300-1 | Blower Discharge Pressure Indicator | Filter Blower Area |
PSH | 300-1 | Blower Discharge High Pressure Switch | Filter Blower Area |
TSH | 300-1 | Blower Discharge High Temperature Switch | Filter Blower Area |
TI | 300-1 | Blower Discharge Temperature Indicator | Filter Blower Area |
LS | 300-8-1 | Low-Low Level Float Switch | Filter Area Sump |
LS | 300-8-2 | Low Level Float Switch | Filter Area Sump |
LS | 300-8-3 | High Level Float Switch | Filter Area Sump |
LS | 300-8-4 | High-High Level Float Switch | Filter Area Sump |
PE/PIT | 800-1 | Suction Pressure Element/Transmitter | Highland Pump Station |
FIT/FE | 800-1 | Magnetic Flow Meter | Highland Pump Station |
PE/PIT | 800-2 | Discharge Pressure Element/Transmitter | Highland Pump Station |
PI | 800-1,2,3 | Pump Pressure Indicator | Highland Pump Station |
TIT/TE | 800-1 | Room Temperature Element/Transmitter | Highland Pump Station |
YS | 800-1 | Door Entry Alarm | Highland Pump Station |
YS | 800-2 | Water on Floor Alarm | Highland Pump Station |
PE/PT | 802-2 | Inlet Pressure Element/Transmitter | 7th Street Reservoir Valve Building |
ZIT | 802-1 | Valve Position Indicator/Transmitter | 7th Street Reservoir Valve Building |
PE/PIT | 802-3 | Outlet Pressure Element/Transmitter | 7th Street Reservoir Valve Building |
SOV | 802-1 | PRV Solenoid Valve | 7th Street Reservoir Valve Building |
TS | 802-1 | Room Temperature Switch | 7th Street Reservoir Valve Building |
DS | 802-1 | Door Switch | 7th Street Reservoir Valve Building |
LSH | 802-1 | High Level Switch | 7th Street Reservoir |
PE/PIT | 802-1 | Reservoir Level Pressure Element/Transmitter | 7th Street Reservoir |
PE/PIT | 801-1 | Reservoir Level Pressure Element/Transmitter | Highland Reservoir |