Main Water Treatment Plant Building
All process areas are heated with natural gas fired units with the exception of the Chlorine Room. The Chlorine Room and Highland Reservoir Vault are heated with an electric unit heates. All heating units are controlled by thermostat, which provides power to the heating element and, for the wall heaters, enables the fan to run. When the thermostat is satisfied, the fan is stopped and the electrical heating element is disabled. The thermostats may be turned to OFF when heating is not required at all. Two destratification fans with wall mounted speed controls are used to disperse the heat in the upper Clarifier Area to the lower portion of the room.
The Electrical Room and Office are equipped with ductless mini-split air conditioning units. The Chlorine Room is equipped with two new exhaust fans that discharge through the room to atmosphere. Equipment existing prior to the 2019-2020 upgrades is not covered in this section.
Heating and Ventilation Equipment1
Equipment Number | Description | Manufacturer |
Water Treatment Plant Building | ||
UH-03 | Fuel-Fired Unit Heater | Modine, Model HD125 |
UH-04 | Fuel-Fired Unit Heater | Modine, Model HD125 |
UH-05 | Fuel-Fired Unit Heater | Modine, Model HD100 |
UH-06 | Fuel-Fired Unit Heater | Modine, Model HD100 |
EF-3 | Exhaust Fan | Cook, GC-168 |
EDH-1 | Inline Duct Heater | Neptronic, DF CIOOH |
Chlorine Room | ||
EF-1 | Exhaust Fan | Cook, ACED-100C17DEC |
EF-2 | Exhaust Fan | Cook, ACED-100C17DEC |
SF-1 | Supply Fan | Cook, 90SQN17DEC |
EH-1 | Electric Wall Heater | Q-Mark, MUH03-81 |
Highland Booster Pump Station | ||
UH-01 | Fuel-Fired Unit Heater | Modine, Model HD125 |
UH-02 | Fuel-Fired Unit Heater | Modine, Model HD75 |
Highland Reservoir Vault | ||
EH-2 | Electric Wall Heater | Q-Mark, CWH3180F |